Circuit Breaker

MCP331000

MCP331000
(NSN) National Stock Number
5925-00-005-3114
Federal Supply Classification
5925 Circuit Breakers
Item Name Code
00136
Schedule B Code
8536200040
Summary

Multipole-single actuator type body style, 6.000 inches nominal body length, 4.125 inches nominal body width, 3.375 inches nominal body height, 5.062 inches nominal center to center distance between terminals parallel to length, 1.375 inches nominal center to center distance between terminals parallel to width

DAC HCC DMIL RNCC
E - - 5
RNVC SADC MSDS RNAAC
9 - - TX
Identification

A device with means other than fuses for automatically opening the circuit in which it is installed when the current varies from the predetermined value for which the device is set. May include provisions for manual operation. At least one set of contacts must be in series with the actuating element(s). A combination of semiconductor and passive devices may be used in lieu of contacts. For automatically operated items in which the actuating (tripping) element and contacts are not in series, see relay (as modified). For items which are operated both manually and automatically but the actuating elements and contact are not in series, see relay-switch. Excludes:circuit breaker box and magneto "breaker" assemblies. See also switch (as modified); and controller.

INC FIIG Concept Condition
00136 A030A0 - 1
Specifications
Body Style
multipole-single actuator type
Details The style designation indicating the configuration that most nearly corresponds to the appearance of the body.
Body Length
6.000 inches nominal
Details A measurement of the longest dimension of the body,in distinction from width.
Body Width
4.125 inches nominal
Details A measurement taken at right angles to the length of the body,in distinction from thickness.
Body Height
3.375 inches nominal
Details A measurement from the bottom to the top of the body,in distinction from depth.
Center To Center Distance Between Terminals Parallel To Length
5.062 inches nominal
Details The center to center distance between terminals parallel to the length of the item.
Center To Center Distance Between Terminals Parallel To Width
1.375 inches nominal
Details The center to center distance between terminals parallel to the width of the item.
Unthreaded Mounting Hole Diameter
0.187 inches nominal
Details The length of a straight line which passes through the center of an unthreaded mounting hole,and terminates at the circumference.
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
4.500 inches nominal
Details The distance between centerlines of mounting facilities parallel to the length of the item.
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
1.375 inches nominal
Details The distance between centerlines of mounting facilities parallel to the width of the item.
Fragility Factor
moderately rugged
Details The measure of sensitivity of the item to be packaged. a factor used by packaging engineers in devising proper cushioning in a package.
Boss Height
0.125 inches nominal
Details None.
Pole Quantity
3
Details The number of poles included in the item.
Mounting Facility Type And Quantity
4 unthreaded hole
Details Indicates the type and number of facilities by which the item is mounted.
Storage Type
general purpose warehouse
Details Indicates the type of storage space required for an item in order to provide the degree of protection necessary to maintain serviceability standards.
Maximum Continuous Load Current Rating Per Pole
100.0 amperes ac all locations
Details The maximum current load that each pole is rated to carry continuously.
Operating Voltage Type And Rating Per Pole In Volts
600.0 ac all locations
Details Indicates the type and value of operating voltage for which each pole is designed to operate,expressed in volts.
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
14000.0 ac all locations
Details Indicates the type and value of the maximum short circuit current that the item will successfully interrupt,per pole,at the specified rated voltage,expressed in amperes.
Circuit Protection Type
overcurrent all locations
Details Indicates the type of electrical condition that will cause the device to trip.
Trip Release Method
magnetic all locations
Details The means by which the trip mechanism is released.
Trip Release Characteristic
time delay all locations
Details Denotes the type of trip release action.
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
130.0 all locations
Details The continuous current rating per pole at which the device must trip in a specified time,expressed in percent.
Reset Method
manual
Details The means provided to reposition the mechanism so that the device is ready to function.
Main Contact Tripping Mechanism Type
trip free
Details Indicates the type of mechanism provided for tripping main contacts.
Manual Actuator Type And Quantity
1 toggle
Details Indicates the type and number of actuators provided for manual control.
Actuator Function
trip-reset
Details Denotes the action imparted by actuator operation.
Actuator Position Designation
at pole two
Details An indication of the designated position of the actuator.
Internal Trip Release Configuration
series trip all locations
Details The basic internal electrical configuration of the trip mechanism.
Trip Delay Time In Seconds Per Rated Continuous Current
200.000 maximum at 200 pct all locations
Details The length of time,expressed in seconds,that an overload may exist before the device will trip at a specified continuous current.
Inclosure Protection Type For Which Designed
fungus resistant and moisture resistant
Details Indicates the type of protection for which the inclosure is designed.
Case Material
plastic
Details The chemical compound or mechanical mixture properties of which the case is fabricated. please use mrc matt with isac table 0326 in place of this canceled mrc.
Frequency In Hertz
60.0 all locations
Details The cycles per second /hertz/ of the alternating current.
Terminal Type And Quantity
6 compression
Details Indicates the type and number of terminals for providing electrical connection.
Master-Cross Reference List
Part CAGE DAC HCC RNCC RNVC MSDS RNAAC
C528-11 99167 5 - 5 2 - TX
4994D97G27 89946 5 - 5 9 - TX
MCP331000R 89946 E - 3 2 - TX
23739 20874 5 - 5 9 - TX
Material and Special Handling
Hazardous material, precious metals, criticality, and electrostatic discharge indicators.
HMIC PMIC ESD/EMI Criticality
P U - -
Freight
Universal / National Freight and Handling Information
UFC HMC LTL LCL
35205 - W -
RVC WCC TCC SHC
- 72D Z 9

Certified Supplier

Order with confidence. We are a valued certified supplier serving customers in the military and aerospace industries.

  • Fast Quote Times
  • Qualified sales team
  • 100% Product Inspections
  • Counterfeit Parts Prevention
Manufacturer
EATON CORPORATION
CAGE: 89946
BEAVER , PA , 15009-1720
UNITED STATES
View Products
FAQs
Frequently asked questions for NSN 5925-00-005-3114
What is the NIIN of the NSN 5925-00-005-3114?
The National Item Identification Number (NIIN) of the NSN 5925-00-005-3114 is 00-005-3114
When the NSN 5925-00-005-3114 was assigned to the Federal Catalog?
It was assigned 52 years ago, on Wed, Jun 14, 1972
Does the NSN 5925-00-005-3114 contain any precious metals?
Type/content is unknown
Does the NSN 5925-00-005-3114 contain any hazardous material?
No information in HMIRS

Can't Find It

If you didn't find what you need, don't worry, we're here to help! Our team is ready to help you find exactly what you need. Click below to contact us.

Similar Products
Who we are?

We are one of the largest suppliers of National Stock Number (NSN) parts in the world. Here at NSN Equipment, we live on the cutting edge to give you the best service we possibly can.

And that service is why our customers return to us time and time again. Our credibility and our accolades only serve as testament to our industry-leading nature.

Contact
3555 Agricultural Center Dr.
St. Augustine, FL, 32092
United States
© 2024 NSN Equipment, Inc. All rights reserved.
Made in USA